Weighing room is used for research and scientific experiments and other places dedicated local cleaning equipment, it provides vertical one-way airflow, part of the clean air circulation in the work area, part of the discharge to the nearby area, so that the work area to produce negative pressure, to prevent cross-contamination, used to ensure the high cleanliness of the work area environment.
Configuration and performance
Intelligent information processing, automated operation, in line with pharmaceutical industry regulations;
Can provide a variety of control methods, PLC intelligent control system and configuration of LED touch screen,
Real-time monitoring and adjustment of better operating conditions;
Modular design and facade arc processing technology ensure easy installation and use;
There are explosion-proof, anti-corrosion and other special models to choose from, in order to adapt to harsh field use conditions.
Technical parameter
Model/Parameter | WR112-120 | WR112-200 | WR112-300 |
External dimension(L x Wx H) mm | 1300x1200x2600 | 2000x 2000 x 2600 | 3000x2400x2600 |
Inside dimension(Lx Wx H) mm | 1200x800x2000 | 1900 x 1600 x 2000 | 2900x1800x2000 |
Box material | Stainless steel plate |
Outlet panel | Stainless steel plate/polymer flow film |
Cleanliness grade | Same as the background wall |
Mean wind speed(m/s) | 0.45m/s ±20% |
Differential pressure gauge | Pointer/digital display |
Air partition | Soft curtain/tempered glass/air curtain |
Filter | G4 Primary filter +F8 Medium filter (EN779) +H14 High efficiency filter (EN1822) |
Control mode can be implemented | Siemens touch screen +PLC, can achieve pressure difference, wind speed online monitoring, fault alarm, audit tracking, etc |
Power source | 220V /50HZ 或 380V /50HZ |
Power(w) | 400 w | 800 w | 2000 w |